AI4 - (E) 4× M12 (TH)
for thermo elements
Input
Conversion time (analog) max. 300 ms (per channel)
Type K, N, E, J, R
Resolution (analog) 15 Bit + sign
Accuracy max. ±2%, cold junction compensation
Connection 2-wire input; TH+x, TH-x
Internal communication
Module supply via system connection
Current consumption max. 25 mA from system, max. 45 mA externally (UI)
Connections
Fieldbus Ribbon cable connection
Sensor-system/actuator supply 4× spring clamp plug-in terminals, max. 2.5 mm² (max. 12 A)
I/O ports 12× spring clamp plug-in terminals, max. 2.5 mm²
General data
Protection IP20
Mounting method DIN-rail mountable (EN 60715)
Temperature range 0...+55 °C (storage temperature -20...+85 °C)
Dimensions H×W×D 117×56×47 mm
Diagnostic
Communication status via LED
Diagnostic via LED per module
Diagnostic via BUS per module and channel
Monitoring - under voltage yes
Monitoring - no voltage no
Short-circuit and overload yes
Wire break upper/lower limit overload per channel via LED and BUS
Commercial data
country of origin DE
customs tariff number 85176200
EAN 4048879049177
eClass 27242601
Pakke-enhed 1
 
Oplysninger vedrørende artikel:
  • Hent Datablad
  • Hent Approvals and certificates 56240_E201820_NRAQ_ul_z_a.pdf
  • Hent Approvals and certificates 56240_E201820_NRAQ7_ulc_z_a.pdf
  • Hent Approvals and certificates 56240_957-04.16_ce_z_c.pdf
  • Hent Drawing Files 56240_stp_x_a.zip
  • Hent Drawing Files 56240_p8_2_50.zip
  • Hent Drawing Files 56240_dxf_x_a.zip
  • Hent Drawing Files 56001_p8_2_50.zip
  • Hent Installation Instructions 56230_ina_6_12.pdf
  • Hent Kina RoHS Information EPUP-20_CHR_x_1.pdf
  • Hent Manuals 56035_hdb_x_16.zip
  • Hent Manuals 56030_hdb_x_13.zip
  • Hent Software and driver Cube20_Beschriftung.xls
cULus
* Plus moms og forsendelsesomkostninger