Har du spørgsmål om vores produkter? Vores eksperter er klar til at hjælper dig! Ring til os +45 9635 0606

Du vil måske også kunne lide

Digital inputs/outputs
DIO12 IOL4 (IRT)
Ethernet 10/100 Mbit/s; M12, D-coded
M12 Power, 5-pole, L-coded
M12, 5-pole, A-coded
IO-Link Master V1.12
Connection cables are in the online shop under "Connection Technology". Housing fully potted.
Input
Sensor supply US 24 V DC (EN 61131-2), max. 200 mA (M12 female)/max. 1 A (IO-Link female), short-circuit and overload protected
Type for 3-wire sensors or mechanical switches, PNP, IO-Link Devices
Output
Actuator supply UA 24 V DC (EN 61131-2), max. 9 A
Switching current per output max. 1.6 A (short-circuit and overload protected)
Lamp load 10 W
Connections
Fieldbus Ethernet 10/100 Mbit/s; M12, D-coded
Sensor-system/actuator supply M12 Power, 5-pole, L-coded, 2× max. 16 A
I/O ports M12, 5-pole, A-coded
General data
Protection IP67
Mounting method 2-hole screw mounting, compatible with I/O modules of MVK model range
Dimensions H×W×D 37×63×225 mm
Temperature range -25...+55 °C (storage temperature -25...+70 °C)
IO-Link
IO-Link 4× Master
Operating modes COM1; COM2; COM3 (automatic)
Transfer parameters 32 Byte (per IO-Link port)
Port Class Class B (not galvanically separated)
Specification IO-Link Master V1.12
PROFINET
FSU (Fast-Start-Up) max. 500 ms
Shared Device/Input yes, for 2 controls
PROFINET Netload Class III
Specification V2.3, Conformance Class C (IRT)
Addressing DCP
Parameterization
PIN 4 Input/Output (port X0...X7); IO-Link Master (port X4...X7)
PIN 2 Input/Output (port X0...X7); U-Actuator IO-Link Class B (port X4...X7)
Diagnostic
Communication status via LED
Diagnostic via LED per module and channel
Diagnostic via BUS per module and channel
Monitoring - under voltage yes
Monitoring - no voltage yes
Short-circuit and overload yes
Actuator warning per channel via LED and BUS
Cable break per port
Commercial data
country of origin DE
customs tariff number 85389099
EAN 4048879778671
eClass 27242604
Pakke-enhed 1
 
Oplysninger vedrørende artikel:
  • Hent Datablad
  • Hent Approvals and certificates 55172_23-09.19_ce_z_a.pdf
  • Hent Approvals and certificates 55172_E201820-NRAQ7_ulc_z_a.pdf
  • Hent Approvals and certificates 55172_E201820-NRAQ_ul_z_a.pdf
  • Hent Approvals and certificates 55172_Z12276-Z40280-11.07.2022-v2.33_pn_z_b.pdf
  • Hent China RoHS information EPUP-25_CHR_x_1.pdf
  • Hent Configuration Files 55130_Impact67_Kfg_x_14.zip
  • Hent Drawing Files 55150_dxf_x_a.zip
  • Hent Drawing Files 55170_stp_x_a.zip
  • Hent Drawing Files 55172_p8_2_10.zip
  • Hent Installation Instructions 55172_ina_x_10.zip
  • Hent Manuals 55170_hdb_x_13.zip
  • Hent Product data 55172_pd_x_12.zip
  • Hent Software and driver 10501019_IO-Link-Device-Tool_TRB_x_48.zip
  • Hent Software and driver 10500955_AutoUpdateX_x_23.zip
cULus
PROFINET
IO-Link
* Plus moms og forsendelsesomkostninger