CUBE20 AO4 U/I
Art.No.: | 56220 |
Weight: | 0.19 kg |
Country of origin: | CZ |
Out of Stock - Contact Us for Availability
Description
Expansion module
AO4 - (E) U/I
AO4 - (E) U/I



Technical Data
Output
Resolution (analog) | 15 Bit + sign |
---|---|
Conversion time (analog) | max. 1 ms (per channel) |
Galvanic isolation | 500 V DC between inputs and internal communication |
Accuracy | max. 0.5% |
General data
Mounting method | DIN-rail mountable (EN 60715) |
---|---|
Temperature range | 0...+55 °C (storage temperature -20...+85 °C) |
Protection | IP20 |
Dimensions H×W×D | 117×56×47 mm |
Diagnostic
Communication status | via LED |
---|---|
Diagnostic via BUS | per module and channel |
Diagnostic via LED | per module and channel |
Actuator warning | per channel via LED and BUS |
Monitoring - under voltage | yes |
Monitoring - no voltage | no |
Wire break upper/lower limit overload | per channel via LED and BUS |
Short-circuit and overload | yes |
Internal communication
Current consumption | max. 25 mA from system, max. 90 mA externally (UI), idle load |
---|---|
Module supply | via system connection |
Voltage output signals
Input range | ±10 V DC, 0...10 V DC |
---|---|
Load | min. 1 kΩ, (EN 61131-2) |
Current outputs
Input range | 0...20 mA, 4...20 mA |
---|---|
Load | max. 60 Ω (EN 61131-2) |
Connections
Fieldbus | Ribbon cable connection |
---|---|
Sensor-system/actuator supply | 4× spring clamp plug-in terminals, max. 2.5 mm² (max. 12 A) |
I/O ports | 24× spring clamp plug-in terminals, max. 2.5 mm² |
Commercial data
ECLASS-6.0 | 27242601 |
---|---|
ECLASS-6.1 | 27242601 |
ECLASS-7.0 | 27242601 |
ECLASS-8.0 | 27242601 |
ECLASS-9.0 | 27242601 |
ECLASS-10.1 | 27242601 |
ECLASS-11.1 | 27242601 |
ECLASS-12.0 | 27242601 |
ETIM-5.0 | EC001596 |
customs tariff number | 85176200 |
EAN | 4048879049207 |
Packaging unit | 1 |
Accessories
---- Terminal Strip ----